You almost never need to drain the whole heating system to deal with one radiator. If both of its valves shut off properly, that radiator can be emptied on its own in under an hour, with the boiler, the other radiators and the hot water left alone. The whole job depends on those two valves actually closing, so most of this guide is about checking that before you undo anything.
Why you would drain a single radiator
Usually to take it off the wall for decorating, to change a valve that is weeping from its body or tail, or to replace a radiator that has rusted through. Autumn is when most people find out they need to: the first proper heating cycle warms joints that have sat cold since spring, and a valve that was dry in August starts weeping in October. If that is why you are here, radiator leaking from the valve explains which part of the valve is usually at fault, because some weeps can be dealt with without draining anything.
What you need
- Two adjustable spanners, or one spanner and a grip wrench to hold the valve body still.
- A radiator bleed key.
- A shallow tray that fits under the valve: a roasting tin or a wallpaper tray works. A bucket will not fit under most tails.
- A jug to empty the tray, and old towels. The water is black with sludge and stains carpet permanently.
- The manual cap for the thermostatic valve, often called the decorator's cap. If you do not have one, read the next section before you go further.
Before you start: make sure both valves really shut
Every radiator has two valves at the bottom. One is the valve you turn to set the temperature, usually a thermostatic valve with a numbered head. The other is the lockshield, a plain valve under a plastic cap, which was set when the system was balanced and is not meant to be touched day to day. Radiator valve types has pictures of each.
The thermostatic head turned to zero or the snowflake is not a shut-off. That setting is frost protection. It only closes the valve until the room gets cold, and on a worn valve the pin underneath may not seal at all. To shut it properly, unscrew the head and fit the manual cap in its place, then turn the cap fully clockwise.
Count the lockshield turns. Pull off the plastic cap and close the lockshield with a spanner or small grip, clockwise, counting quarter turns until it stops. Write the number on masking tape and stick it to the pipe. When the radiator goes back on, you reopen it the same number of turns, or that radiator will take more than its share of hot water and starve rooms further along the circuit. Lockshield valve explains the setting in more detail.
Now test the seal before you drain. Open the bleed screw a quarter turn with a cloth under it. On a sealed system, a short hiss and then a trickle that stops is what you want. If water keeps coming steadily after a minute, one of the valves is passing and you should not open the union nut. Close the bleed screw and skip to when the valves will not close.
How to drain the radiator, step by step
- Heating off, and cold. Switch the heating off at the programmer and give the radiator time to go cold. System water can run hot enough to scald, and it comes out under pressure the moment the union moves. Check with the back of your hand.
- Both valves shut, as above: manual cap on the thermostatic end, lockshield closed and counted.
- Tray and towels down under whichever valve gives you most room.
- Hold the valve body and slacken the union. The union is the large nut joining the valve to the radiator tail. Put one spanner on the valve body to stop it turning, and use the other to undo the union anticlockwise, looking at it from the radiator side. Hold the valve still: if it twists, you strain the pipe under the floor, and that joint is the one you will not see leaking.
- Crack it, do not remove it. A turn or so is enough. Water will start to run from the joint into the tray. Control the flow with the nut: tighten it slightly when the tray is getting full, empty the tray, then loosen it again.
- Open the bleed screw. Once the flow slows, open the bleed screw at the top so air can get in behind the water. The radiator drains much faster with air in it. Keep emptying the tray.
- Wait for it to stop dripping. Some water always stays in the bottom of the panel. If you are lifting the radiator off, undo the other union too and tip it towards the tray before you carry it anywhere, with two people.
- Protect the open valves with a bag and tape, so grit stays out and a slightly passing valve does not drip on the floor.